| Model | CJMM6RT/A-125 | CJMM6RT-160 | CJMM6RT-250 | ||||||||||
| Raamstroom In | 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A, | 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A, 140A, 160A | 100A, 125A, 140A, 160A, 180A, 200A, 225A, 250A | ||||||||||
| Kortsluitingbreuk kapasiteitskode | C | S | M | H | C | S | M | H | C | S | M | H | |
| Aantal pale | 3P/4P | ||||||||||||
| Gegradeerde werk spanning Ue (V), WS | WS400V | ||||||||||||
| Gegradeerde isolasie spanning Ui (V) | 1000V | ||||||||||||
| Gegradeerde impulsweerstand spanning Uimp (kV) | 8kV | ||||||||||||
| Gegradeerde diens kortsluiting breekvermoë Ics (%Icu) | AC 400V | 5kA | 10kA | 18kA | 50kA | 5kA | 10kA | 10kA | 50kA | 5kA | 8kA | 10kA | 50kA |
| Gegradeerde uiteindelike kortsluiting breekvermoë Icu (kA) | 10kA | 20kA | 36kA | 50kA | 8kA | 20kA | 20kA | 50kA | 8kA | 15kA | 20kA | 50kA | |
| Selektiewe kategorie | Klas A | ||||||||||||
| Oorstroomvrystellingtipe | Termomagnetiese tipe | ||||||||||||
| CJMM6RT-oorsig afmeting (mm) Breedte (B) * Lengte (L)*Hoogte (H) | Raamstroom | CJMM6RT/A-125 | CJMM6RT-160 | CJMM6RT-250 | |||||||||
| Aantal pale | 3P | 4P | 3P | 4P | 3P | 4P | |||||||
| Breedte | 75 | 100 | 90 | 120 | 105 | 140 | |||||||
| Lengte | 130 | 130 | 155 | 155 | 165 | 165 | |||||||
| Hoogte/gesigbedekking | 68 | 68 | 68 | 82 | 68 | 82 | 68 | 88 | 68 | 88 | |||
| Hoogte/handvatsel | 94.5 | 94.5 | 94 | 108 | 94 | 108 | 96 | 116 | 96 | 116 | |||
| Model | CJMM6RT-400 | CJMM6RT-630 | CJMM6RT-800 | CJMM6RT-1250 | CJMM6RT-2000 | ||||||
| Raamstroom In | 320A, 350A, 400A | 400A, 500A, 630A | 630A, 700A, 800A | 1000A, 1250A | 1600A | ||||||
| Kortsluitingbreuk kapasiteitskode | M | H | M | H | M | H | M | H | M | H | |
| Aantal pale | |||||||||||
| Gegradeerde werk spanning Ue (V), WS | |||||||||||
| Gegradeerde isolasie spanning Ui (V) | |||||||||||
| Gegradeerde impulsweerstand spanning Uimp (kV) | |||||||||||
| Gegradeerde diens kortsluiting breekvermoë Ics (%Icu) | AC 400V | 50kA | 50kA | 50kA | 50kA | 50kA | 65kA | 50kA | 65kA | 50kA | 85kA |
| Gegradeerde uiteindelike kortsluiting breekvermoë Icu (kA) | 50kA | 50kA | 50kA | 50kA | 65kA | 85kA | 65kA | 85kA | 50kA | 100kA | |
| Selektiewe kategorie | |||||||||||
| Oorstroomvrystellingtipe | |||||||||||
| CJMM6RT-oorsig afmeting (mm) Breedte (B) * Lengte (L)*Hoogte (H) | Raamstroom | CJMM6RT-400 | CJMM6RT-630 | CJMM6RT-800 | CJMM6RT-1250 | CJMM6RT-2000 | |||||
| Aantal pale | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | |
| Breedte | 140 | 184 | 140 | 184 | 210 | 280 | 210 | 280 | 210 | 280 | |
| Lengte | 257 | 257 | 257 | 257 | 275.5 | 275.5 | 275.5 | 275.5 | 340 | 340 | |
| Hoogte/gesigbedekking | 103 | 103 | 103 | 103 | 103 | 103 | 103 | 103 | 141 | 141 | |
| Hoogte/handvatsel | 152 | 152 | 152 | 152 | 152 | 152 | 152 | 152 | 244 | 244 | |
Let wel: Die hoogte vanaf die onderkant van die basis tot die (gesigbedekking/handvatsel)
| NO | In(A) | Parameters | Indeksvereistes |
| 1 | 160-1250 | Oorbelasting langvertraging-uitskakeling-instellingsstroom (A) | 0.7~1.0ln verstelbaar (opsioneel) |
| 2 | 0.8~1.0ln verstelbaar (opsioneel) | ||
| 3 | Kortsluit-oombliklike uitskakeling-instellingsstroom (A) | 5ln~10ln verstelbaar (opsioneel) | |
| 4 | Kortsluitbeskerming | Wanneer 0.8*(5ln/10ln), sal dit nie binne 0.2s werk nie | |
| 5 | Wanneer 1.2*(5ln/10ln), sal dit binne 0.2s werk | ||
| 6 | 125 | Oorbelasting langvertraging-uitskakeling-instellingsstroom (A) | 0.7~1.0ln verstelbaar (opsioneel) |
| 7 | 0.8~1.0ln verstelbaar (opsioneel) |